(c)2020 IEEE. Personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution to servers or lists, or to reuse any copyrighted component of this work in other works must be obtained from the IEEE.
All documents in ORBi are protected by a user license.
Abstract :
[en] A reduced-order, “grey-box” model of an active distribution network, intended for dynamic simulations of the transmission system, is derived. The network hosts inverter-based generators as well as static and motor loads, whose dynamic parameters are affected by uncertainty. This issue is addressed using Monte-Carlo simulations. The parameters of the equivalent are adjusted to match as closely as possible the average of the randomized responses, while their dispersion is accounted for through the weights of the weighted least-square minimization. A procedure is used to remove from the identification the parameters with negligible impact. To avoid over-fitting, the
equivalent is tuned for multiple large-disturbance simulations. A recursive procedure is used to select the smallest possible subset of disturbances involved in the least-square minimization. Simulation results with a 75-bus MV test-system are reported. They show that the equivalent is able to reproduce with good accuracy the discontinuous controls of inverter-based generators, such as reactive current injection and tripping.