Paper published in a book (Scientific congresses and symposiums)
State Reconstruction from a Limited Number of Synchronized Phasor Measurements: Application to Voltage Instability Detection
Glavic, Mevludin; Van Cutsem, Thierry
2012In Proceedings of the IEEE PES General Meeting
 

Files


Full Text
paperIEEE_PES_2012.pdf
Author postprint (291.93 kB)
Download

© 2012 IEEE. Personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution to servers or lists, or to reuse any copyrighted component of this work in other works must be obtained from the IEEE.


All documents in ORBi are protected by a user license.

Send to



Details



Keywords :
Long-term voltage instability; instability detection; wide-area monitoring; sensitivity analysis; synchronized phasor measurements; unobservability; state estimation; state reconstruction; weighted least squares; constrained optimization
Abstract :
[en] This paper deals with the performance of the wide-area monitoring previously proposed by the authors in [1], [2] for early detection of voltage instability, when a limited number of synchronized phasor measurements is available. This sensitivity-based scheme assumed that phasor measurements are sufficient in number and location for a state estimator to determine the voltages at all buses of the region prone to voltage instability. This paper demonstrates that the method still performs well when relying on bus voltages obtained from a state reconstruction procedure exploiting a limited number of synchronized phasor measurements which do not make the region of concern observable. The state reconstruction is formulated as the minimization, under constraints, of a weighted least square objective involving the available phasor measurements together with bus power pseudo-measurements relative to a reference state. The presented results relate to a 52-bus system with phasor measurements obtained from detailed time simulation of a long-term voltage unstable evolution triggered by a large disturbance. [1] M. Glavic, T. Van Cutsem, “Wide-Area Detection of Voltage Instability From Synchronized Phasor Measurements. Part I: Principle,” IEEE Trans. Power Syst., Vol. 24, No. 3, pp. 1408-1416, Aug. 2009 [2] M. Glavic, T. Van Cutsem, “Wide-Area Detection of Voltage Instability From Synchronized Phasor Measurements. Part II: Simulation Results,” IEEE Trans. Power Syst., Vol. 24, No. 3, pp. 1417-1425, Aug. 2009
Disciplines :
Electrical & electronics engineering
Author, co-author :
Glavic, Mevludin 
Van Cutsem, Thierry  ;  Université de Liège - ULiège > Dép. d'électric., électron. et informat. (Inst.Montefiore) > Systèmes et modélisation
Language :
English
Title :
State Reconstruction from a Limited Number of Synchronized Phasor Measurements: Application to Voltage Instability Detection
Publication date :
July 2012
Event name :
IEEE Power Engineering Society General Meeting
Event organizer :
IEEE
Event place :
San Diego (CA), United States
Event date :
du 22 au 26 juillet 2012
By request :
Yes
Audience :
International
Main work title :
Proceedings of the IEEE PES General Meeting
Funders :
F.R.S.-FNRS - Fonds de la Recherche Scientifique [BE]
Available on ORBi :
since 10 July 2012

Statistics


Number of views
121 (8 by ULiège)
Number of downloads
282 (3 by ULiège)

Scopus citations®
 
3
Scopus citations®
without self-citations
2

Bibliography


Similar publications



Contact ORBi