© 2009 IEEE. Personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution to servers or lists, or to reuse any copyrighted component of this work in other works must be obtained from the IEEE.
All documents in ORBi are protected by a user license.
Abstract :
[en] In the presence of induction motor loads, long-term voltage instability may end up in a sharp voltage decrease, which makes the tuning of undervoltage load shedding more delicate. This paper first investigates the ability of a purely distributed load shedding scheme, previously proposed by the authors, to cope with these situations. Owing to difficulties to reconcile dependability and security, an alternative wide-area protection is considered. The latter consists of generators sending overexcitation signals to the load shedding controllers in order to allow the latter to act faster. Detailed time simulations of a test system are reported.
Commentary :
(c)2009 IEEE. Personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution to servers or lists, or to reuse any copyrighted component of this work in other works must be obtained from the IEEE.
Scopus citations®
without self-citations
8