Revealing and optimizing the heating performance of diffuse ceiling ventilation in cold climates
Guo, Rui; Peng, Pei; Zhang, Chen et al.
2026 • In Applied Thermal Engineering, 310, p. 134022
Peer Reviewed verified by ORBi
 

Files


Full Text
Revealing and optimizing the heating performance of diffuse ceiling.pdf
Publisher postprint (4.07 MB) Creative Commons License - Attribution, Non-Commercial, No Derivative
Download

All documents in ORBi are protected by a user license.

Send to



Details



Keywords :
Diffuse ceiling ventilation; Space heating; Convective heat transfer; Building energy simulation; Multi-objective optimization
Abstract :
[en] Diffuse ceiling ventilation (DCV) has shown promising cooling performance in cold climates, but its applicability to space heating remains uncertain due to buoyancy-driven stratification and delayed heat delivery from ceiling-level supply. The lack of validated inside surface convection algorithms for DCV under heating conditions has further hindered reliable energy assessment and design optimization. This study develops a heating-oriented evaluation and optimization approach for DCV by integrating full-scale experimental validation, zone-specific convective heat transfer modelling, dynamic building energy simulation, and multi-objective optimization. Full-scale measurements were used to identify appropriate inside surface convection algorithms for the plenum and occupied zone, revealing that zone-resolved convection treatment is essential for reliable DCV heating simulation. Using the identified modelling basis, seasonal simulations of a cold-climate office showed that DCV reduced HVAC electricity use by 15.5% compared with a fully mixed MV reference, while maintaining a similar modelled average predicted percentage of dissatisfied (PPD). The normalized knee-point solution further increased the HVAC electricity reduction relative to MV to 23.1% by coordinating start-up heating, heating setpoint, and material-layer thickness, while reducing average PPD from 7.3% to 7.0% relative to baseline DCV. These results support DCV as a candidate low-energy heating strategy for comparable cold-climate offices under the investigated modelling and design-control assumptions.
Disciplines :
Architecture
Author, co-author :
Guo, Rui
Peng, Pei
Zhang, Chen
Rashidov. Jasur
Khushvaqtovna, Samiyeva Shakhnoza
Zhuang, Chaoqun
Gao, Yafeng
Wang, Julian
Attia, Shady  ;  Université de Liège - ULiège > Urban and Environmental Engineering  ; Université de Liège - ULiège > Département ArGEnCo > Techniques de construction des bâtiments
Language :
English
Title :
Revealing and optimizing the heating performance of diffuse ceiling ventilation in cold climates
Publication date :
15 December 2026
Journal title :
Applied Thermal Engineering
ISSN :
1359-4311
eISSN :
1873-5606
Publisher :
Elsevier, United Kingdom
Volume :
310
Pages :
134022
Peer reviewed :
Peer Reviewed verified by ORBi
Development Goals :
11. Sustainable cities and communities
3. Good health and well-being