© 2011 IEEE. Personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution to servers or lists, or to reuse any copyrighted component of this work in other works must be obtained from the IEEE.
All documents in ORBi are protected by a user license.
Abstract :
[en] Abstract—In power system dynamic models the complex network equations and the various phasors are projected onto reference axes. After a short critical review of commonly chosen reference axes, this letter proposes to use the center-of-inertia at the previous integration time step. This approach is shown to combine the advantages of the center-of-inertia with a sparser Jacobian structure and an easier handling of network splits.