Article (Scientific journals)
Development and validation of a condenser three zones model
Cuevas, Cristian; Lebrun, Jean; Lemort, Vincent et al.
2009In Applied Thermal Engineering
Peer Reviewed verified by ORBi
 

Files


Full Text
Cuevas et al., 2009.pdf
Publisher postprint (926.63 kB)
Request a copy

All documents in ORBi are protected by a user license.

Send to



Details



Keywords :
Air-cooled condenser; Modelling; Critical pressure; R134a
Abstract :
[en] A general and simple ‘‘deterministic” model of a refrigeration condenser is presented. The model assumes that the condenser can be divided into three distinct zones on the refrigerant side: the vapour de-superheating zone, the two-phase zone and the sub-cooled liquid zone. The model inputs are the air supply temperature, the air mass flow rate, the refrigerant supply temperature (or the over-heating), the exhaust sub-cooling and the refrigerant mass flow rate. The model is able to identify the pressures and temperatures in each zone and the corresponding heat flows. The model also gives the geometrical repartition among the zones and the pressure drop on air-side. The condenser model is validated with a total of 183 tests. Testing conditions cover a very wide domain, including pressures up to 40 bars with refrigerant R134a. The model is able to predict with a probability of 95% the condenser supply pressure within a confidence interval of +0.5 and 0.1 bar. This means a condenser power confidence interval within 200 and +100 W, which is considered here as acceptable. Refrigerant pressure drop is predicted with a higher error, but it is attributed to measuring uncertainty. On the other hand, air pressure drop is predicted with a very poor accuracy. Undoubtedly, this is due to the friction factor correlation used in this study which is not the most adequate. Here a difference of 40% is obtained.
Disciplines :
Mechanical engineering
Author, co-author :
Cuevas, Cristian;  Universidad de Concepción > Departamento de Ingeniería Mecánica
Lebrun, Jean ;  Université de Liège - ULiège > Département d'aérospatiale et mécanique > Département d'aérospatiale et mécanique
Lemort, Vincent  ;  Université de Liège - ULiège > Département d'aérospatiale et mécanique > Turbomachines et propulsion aérospatiale
Ngendakumana, Philippe ;  Université de Liège - ULiège > Département d'aérospatiale et mécanique > Thermotechnique
Language :
English
Title :
Development and validation of a condenser three zones model
Publication date :
June 2009
Journal title :
Applied Thermal Engineering
ISSN :
1359-4311
eISSN :
1873-5606
Publisher :
Pergamon Press - An Imprint of Elsevier Science, Oxford, United Kingdom
Peer reviewed :
Peer Reviewed verified by ORBi
Available on ORBi :
since 03 September 2009

Statistics


Number of views
212 (22 by ULiège)
Number of downloads
18 (3 by ULiège)

Scopus citations®
 
19
Scopus citations®
without self-citations
12
OpenCitations
 
11

Bibliography


Similar publications