Influence of contact resistance on shielding efficiency of shielding gutters for HV cables
English
Koroglu, Selim [Yildiz Tech. Univ., Besiktas-Istanbul, Turkey > > > >]
Sergeant, Peter [Universiteit Gent - Ugent > > > >]
V Sabariego, Ruth mailto [Université de Liège - ULiège > Dép. d'électric., électron. et informat. (Inst.Montefiore) > Applied and Computational Electromagnetics (ACE) >]
Dang, Quoc Vuong [Université de Liège - ULiège > Dép. d'électric., électron. et informat. (Inst.Montefiore) > Applied and Computational Electromagnetics (ACE) >]
De Wulf, M. [ArcelorMittal Global R&D Gent, B-9060 Zelzate, Belgium > > > >]
2010
Proceedings of the 14th Biennial IEEE Conference on Electromagnetic Field Computation (CEFC2010)
IEEE
Yes
International
978-1-4244-7059-4
14th Biennial IEEE Conference on Electromagnetic Field Computation (CEFC2010)
May 9-12, 2010
IEEE
Chicago, Illinois
USA
[en] Shielding of buried three phase high voltage cables can be done by placing the cables in conducting ferromagnetic U-shaped gutters covered by plates. In case of a perfect electrical contact between adjacent gutters and between adjacent cover plates, the induced currents in the shield efficiently reduce the field generated in the vicinity of the cables. However, as a perfect contact cannot be guaranteed, it is useful to quantify the effect of a bad electrical contact on the shielding performance. From 2D FEM, 3D FEM and experiments, it is observed that a bad contact does not influence significantly the shielding if the axial length of the plates is relatively long compared to their other dimensions.
http://hdl.handle.net/2268/83255
10.1109/CEFC.2010.5481447
http://ieeexplore.ieee.org/xpl/freeabs_all.jsp?arnumber=5481447

File(s) associated to this reference

Fulltext file(s):

FileCommentaryVersionSizeAccess
Restricted access
10cefc_koruglu_shielding_CEFC2010-1200.pdfPublisher postprint224.73 kBRequest copy

Bookmark and Share SFX Query

All documents in ORBi are protected by a user license.