Article (Scientific journals)
Determining new threshold temperatures for cooling and heating degree day index of different climatic zones of Iran
Roshan, Gh.R.; Ghanghermeh, A.A.; Attia, Shady
2016In Renewable Energy, 101 (2017), p. 156-167
Peer Reviewed verified by ORBi
 

Files


Full Text
Final.pdf
Publisher postprint (4.7 MB)
Download

All documents in ORBi are protected by a user license.

Send to



Details



Keywords :
Meteorology data; Percentile method; Olgyay diagram; Building regulations; Thermal comfort; Base temperature
Abstract :
[en] Iran is a country with a variety of different climates. Determining the threshold temperatures suitable for providing thermal and climatic comfort is necessary and vital to its population well-being. This research presents new threshold temperatures in order to calculate the degree day index required for heating and cooling by taking advantage of the 12 stations that are representative of the diversity of Iran's climate. Using Olgyay diagram, different bioclimatic ranges of 12 weather stations and their frequencies were compiled, processes and analysed. Mean daily data of temperature and relative humidity were used for the period of 1950e2010. Based on the frequencies of temperature readings falling in Olgyay's diagram comfort zone, representive temperature thresholds were selected based on 40 to 60 percentiles or (P20), 25e75% percentile (P50) and the threshold of 10e90% percentile. The findings of this study shows that Mashhad with 29.6% and Anzali with 2.33% of frequencies, have experienced the maximum and minimum days of comfort. After analyzing various percentiles to determine the threshold temperatures, it was observed that there is a little difference among the stations for determining the minimum threshold for the comfort. Differences are more obvious in the maximum thresholds. In total, minimum base temperatures (HDD) belonged to Ardabil stations that were 20.50, 20.90 and 20 deg C for P20, P50 and P80 respectively. The maximum temperature for calculating CDD with values of (P20 ¼ 25 C; P50 ¼ 26.25 C; P80 ¼ 27.50 C) is dedicated to Zabol station. The findings present more reasonable thermal comfort thresholds that can be used by architects, engineers and policy makers to achieve, in turn, more energy efficient homes and high quality indoor and outdoor living environments.
Research center :
SBD Lab
Disciplines :
Architecture
Author, co-author :
Roshan, Gh.R.
Ghanghermeh, A.A.
Attia, Shady  ;  Université de Liège > Département ArGEnCo > Techniques de construction des bâtiments
Language :
English
Title :
Determining new threshold temperatures for cooling and heating degree day index of different climatic zones of Iran
Publication date :
25 August 2016
Journal title :
Renewable Energy
ISSN :
0960-1481
Publisher :
Pergamon Press - An Imprint of Elsevier Science
Volume :
101
Issue :
2017
Pages :
156-167
Peer reviewed :
Peer Reviewed verified by ORBi
Available on ORBi :
since 01 September 2016